4.2 Safety Testing
Safety testing is a mandatory, non-negotiable step in the checkpointfinal whereassembly process that verifies the product poses zero electrical productshazard earnto the rightend touser. beThese trustedtests inare humanthe hands.final It ensuresaudit that hazardousconfirms voltagesthe remainenclosure, isolated,grounding protective earth paths are solid,scheme, and insulation canintegrity withstandcomply real-worldwith stressesinternational withoutregulatory failing.standards Through(e.g., aUL, sequenceCE, ofIEC). earth-bondFailure checks,to insulation resistance,perform and Hipotlog testing,these hiddentests weaknessesresults suchin asnon-compliance, poorlegal connections, moisture, or design oversights are revealed before they can cause shocks, fire, or certification delays. Guarded stationsliability, and strict recipes make the process controlled, while traceable records transform safety from an assumption into hard proof.risk.
4.2.1 PurposeClassification (inand oneTest line)Sequence Mandate
ProveThe thatproduct's safety class dictates the required test sequence and voltages.
A) Device Classification
Product standards require classification based on the protection method:
hazardousClassvoltageIstays boxed-in(Earthed):and that accessibleAccessible metalispartseitheraresolidlydeliberatelyearthedtied(ClasstoI) orproperly insulated(Class II)—with guarded fixtures and rules, not vibes.4.2.2 What you actually test (fast map)- Protective Earth (PE)
/via the main power cord.- Must-Run Tests: Earth Bond, Insulation Resistance (IR), Dielectric Withstand (Hipot).
- Class II (Double Insulated): No Protective Earth connection; safety relies on two layers of reinforced insulation.
- Must-Run Tests: IR, Hipot (Primary – Accessible Metal/SELV).
- Protective Earth (PE)
B) Test Sequence
The test sequence is mandated to prevent equipment damage and ensure reliable results:
Earth Bond – IR (Insulation Resistance) – Hipot (Dielectric Withstand) – (Leakage)
Rule: The system must stop immediately upon any failure. The operator must verify discharge to < 30 V before opening the test enclosure.
4.2.2 Ground Bond Test (PE Continuity)
The Earth Bond —Test verifies the integrity and low resistance of the Protective Earth (PE) path from PEthe power input pin to all accessible metal.metal parts of the enclosure.
- Setup: Test current must be applied from the PE pin to each accessible metal point (trays, lids, heatsinks). 4-wire measurement is preferred.
- Test Current: A high AC current (typically 10 – 25 A for 1 – 2 seconds per specification) is injected to simulate a fault condition.
- Mandate: Scrape pads/serrated washers must be used at the bond points. Failures are often caused by paint under washers or loose lugs.
- Starter Limit: Resistance must be ≤ 0.10 Ω (including test lead compensation).
4.2.3 Insulation Resistance (IR) and Hipot Testing
These tests stress the insulation using different voltage types to find contamination versus structural breakdown.
A) Insulation Resistance (IR)
IR is a gentle DC test — gentle DC check that insulationfinds iscontamination healthy.(e.g., moisture, flux residue) before heavy stress.
- Starter Setup: Typically 500 VDC applied for 30 – 60 seconds dwell.
- Test Pairs: Primary (L+N shorted) – PE/Chassis (Class I).
- Starter Limit: Resistance must be high, generally ≥ 100 MΩ for benign devices.
B) Dielectric Withstand (Hipot)
Hipot applies high voltage (HV) to verify the structural integrity of the insulation.
- Voltage Rule:
—Typicallyshort,1000high-voltageVACstresstobetween2000hazardousVAC or equivalent DC. - Control the Stress: The test must include a ramp-up time of 1 – 2 seconds and
accessibleacircuits.dwell time of 2 – 3 seconds (production) to avoid nuisance trips from capacitive charging. (Failure Management: IfyourEMIspecY-capacitorscallsorit)MOVs cause the AC Hipot test to trip:LeakageswitchCurrentto DC Hipot, increase the ramp time, or use the product's designed test bypass (never snip components).- Acceptance:
—Nowithtripmainsatapplied,spec;measureleakagetouch/earth leakage.
Sequence:current Earthmust Bondbe →within IRthe →defined Hipot →window (Leakage)mA scale for AC; µA for DC).
4.2.4 onStation anySafety fail;and Data Traceability
Due to the high voltages, strict operator safety protocols and rigorous data logging are mandatory.
A) Station Safety Non-Negotiables
- Interlocks: The test fixture must have an interlocked enclosure where the door locks during HV application. An E-stop must be immediately reachable.
- Discharge: The system must enforce discharge to < 30 V before
opening.the door unlocks; a visible "SAFE" lamp is mandatory. - Leads: HV leads must be guarded; alligator clips on painted metal are prohibited.
- Operator Protocol: The ESD strap must be OFF during HV tests. The "one-hand rule" (one hand only in the cabinet) must be enforced if testing without full enclosure.
B) Data and Audit Mandates
The test system must capture and link all test data to the unit's Serial Number (SN).
- Data
Fields:
worst-case Ω for Earth Bond.4.2.3The log must include the Recipe ID, ClassI(I/II),vstimestamp,Classcurrent/voltageIIapplied,(chooseramp/dwell times, and therightresultingplaybook) - Log Integrity: Log results must be stored automatically in the MES; manual edits are prohibited.
Final Checklist
|
|
|
|
| |
Your product standard sets voltages/limits. The values below are starter ranges—always use the recipe from PE/QE.
4.2.4 Station safety (non-negotiables)
Interlocked enclosure; door locks during HV;E-stopreachable.Bleed-downto <30 Vbefore door unlocks; visible “SAFE” lamp.Guarded HV leads; no alligator clips on painted metal.One-hand rule;ESD strap OFFduring HV tests.Dailyself-test: verify outputs, trip, discharge. Log it.
4.2.5 Earth Bond (PE continuity)
What: Drive a high current through the PE path and measure resistance/voltage drop.
Setup
Bond point:PE pin → each accessible metal(trays, lids, heatsinks).Test current:10–25 Afor1–2 s(per spec); 4-wire preferred.Scrape pads/serrated washers in place (23.1/23.2).
Starter limit: R ≤ 0.10 Ω (include test lead compensation).
Fail fast cues: loose lugs, paint under washers, long star-to-star stackups.
4.2.6 Insulation Resistance (IR)
Why before Hipot: it finds contamination/moisture without heavy stress.
Pairs to test (typical)
Primary (L+N shorted) ↔ PE/chassis(Class I).Primary (L+N) ↔ accessible metal/SELV(Class I & II).
Starter setup: 500 VDC, 30–60 s dwell.
Starter limits: ≥ 100 MΩ benign devices; ≥ 10–100 MΩ rugged/EMI-heavy (agree with QE).
Dry to room conditions if humidity just came off a wash/soak.
4.2.7 Hipot (dielectric withstand)
What: apply HV for a short time and ensure no breakdown.
DC vs AC
DC Hipot: tolerant of EMI capacitors, clean leakage reading.AC Hipot: stresses both polarities, sometimes required by spec.
Typical pairs & ranges (use your recipe)
Primary (L+N tied)↔PE/chassis:1000–2000 VACor1200–2800 VDC.Primary↔SELV/accessible circuits: same order of magnitude; higher for Class II.SELV↔chassis: sometimes required (lower voltages).
Control the stress
Ramp1–2 s →Dwell2–3 s (longer for bulky filters) →Dischargeto <30 V.Trip/leakagewindows set per product (mA scale for AC; mA/µA for DC).If EMIY-caps/MOVscause nuisance trips: switch toDC, add ramp, or use the product’s test bypass (if designed). Never snip parts.
4.2.8 Leakage current
(when your standard calls for it)
With mains applied, measure earth/touch leakage in normal and single-fault (e.g., reversed polarity).
Use a compliantleakage testerand the network your spec defines.LogmA RMSand test condition. Limits arestandard-specific—the recipe must encode them.
4.2.9 Special parts to respect
MOVs/Surge suppressorsline↔earth: AC Hipot can make them conduct—preferDCor spec’d bypass.Filters with big Y-caps: expect higher leakage; tunetripandramp.Paint/oxidationat bonds: zero the surface (bare metal) before retesting.
4.2.10 Data & traceability (attach to the SN)
Recipe ID & version,Class (I/II), operator, timestamp.Earth Bond: current, worst-case Ω, points tested.IR: voltage, dwell, MΩ per pair.Hipot: AC/DC, voltage, ramp/dwell, trip setting,max leakage, pairs tested.Leakage(if run): value + condition (normal/single-fault).Fixture/tool IDs andpass/faildecision. No manual edits—MES only.
4.2.11 Acceptance cues (10-second tour)
| ||
| ||
No trip at |
| |
Safety Interlocks |
|
|
Insulation Check |
|
|
Traceability | All parameters (Voltage, Ω, current, ramp time) logged per unit SN. |
|
Rework Rule | If Hipot fails due to paint under lug, surface must be scraped clean and re-tested. | Failure to zero the surface results in recurrence. |
4.2.12 Common traps → smallest reliable fix
4.2.13 Pocket checklists
Before
SKU/Variantscanned→ correct safety recipe loadedInterlock/E-stop OK; strapOFF; leads/labels checkedPE pads bare; serrated washers installed where called
Run
Earth Bond: ≥10 A; worst point≤0.10 ΩIR: 500 VDC; MΩ within limitHipot: pairs per recipe; ramp/dwell/trip set;discharge(If required)Leakage: mains on; values logged
Close
All results toSNin MES; no manual editsFails toNG-QUARwith pair/step notedCage tidy; daily self-test tile green