3.3 Flooring & Grounding Architecture
The floor is the primary electrical foundation of the EPA. It serves as the primarysole ground path for mobile personneloperators, carts, and carts.Autonomous ItGuided mustVehicles be(AGVs). conductiveIf enoughthe flooring system fails (becomes insulative), every step a technician takes generates triboelectric voltage that cannot drain to drainEarth. chargeWithout buta resistivefunctional enoughfloor-ground system, personnel are walking capacitors capable of carrying >3000V directly to protectthe personnel from electric shock.product.
The Resistance Requirements"Sweet (ANSI/ESD S20.20)Spot"
SystemIF Resistance (PersonR)+<Footwear1.0+xFloor):10^5 Ω → THENMust be < $3.5 \times 10^7$ ohmsFail ($35$ megohms) when measured per ANSI/ESD STM97.1.Conductive).Walking Test (Body Voltage Generation):Peak voltage accumulation on a person walking must be < 100 Volts.
Flooring physics requires balancing two opposing risks: static dissipation vs. electrical safety.
Decision Logic: Resistance Zones
Grounding Hardware
Common Point Ground (CPG):Every workstation must have a CPG block that connects the mat, the wrist strap, and the equipment chassis to Earth.Hard Ground vs. Soft Ground:Equipment chassis:Risk:HardLethalGroundshock hazard. If an operator touches live voltage (110/220V), the floor provides a low-resistance path to ground, increasing current flow through the body.
- IF 1.0
Ohm)x 10^5 Ω ≤ R ≤ 1.0 x 10^9 Ω → THEN Pass (Dissipative). Personnel/Mats:Target:SoftThisGroundis(1theMegohmsaferesistoroperatinginwindow.series)Charge drains within milliseconds, but resistance is high enough to limit current to safe levels (< 5mA).- IF R > 1.0 x 10^9 Ω → THEN Fail (Insulative).
- Risk: Charge accumulates faster than it decays. The floor is effectively an insulator.
- Static Decay: The system must drain a 1000V charge to < 100V in
caselessofthanaccidental2 seconds. - Body Voltage Generation (BVG):
- IF peak voltage on walking operator > 100 Volts → THEN Process Fail.
- Action: Verify heel strap contact
withor replace footwear.
- Hard Ground (Chassis): Connect equipment chassis and machine frames directly to Earth (0 Ω impedance). This ensures breaker trips during short circuits.
- Soft Ground (Personnel): Connect wrist straps and table mats to Earth through a 1 Megohm (1 MΩ) current-limiting resistor.
- Why: This resistor prevents the strap from becoming a lightning rod or a lethal path to ground if the operator touches a live
voltage.wire.
- Why: This resistor prevents the strap from becoming a lightning rod or a lethal path to ground if the operator touches a live
Pro-Tip: Never wax an ESD floor with standard commercial polish. Standard wax is a dielectric insulator and will instantly destroy the floor's conductivity. Use only approved ESD-dissipative floor finish.
System Verification (The "Walking Test")
A conductive floor alone provides zero protection if the operator wears standard rubber-soled sneakers. We measure the System Resistance (Floor + Footwear + Person).
Performance Mandate
Grounding Topology
The electrical connection to Earth (Earth Bonding Point) must be robust and distinct from the standard electrical neutral.
Final Checklist
|
|
| Owner |
|
|
| Operations |
|
|
| Facilities |
| < 100 Volts Peak |
| ESD |
Ground | < 1.0 Ω (AC) to Equipment Ground | Annually | Facilities |
Visual Inspection | No cracks, delamination, or wax | Monthly | Facilities |